Amtrol Expansion Tank Sizing Chart

How AMTROL Expansion Tanks Work AMTROL Quality Expansion Tanks2 How It Works2 The Extrol System3 Typical Residential Installation3 Residential Expansion Tank Models4 The Fill-Trol System5 Commercial Non-ASME Models6 Typical Commercial Installation6 Commercial ASME Models7 Sizing the Extrol4 8.

Amtrol expansion tank sizing chart. Request to AMTROL Inc 1400 Division Road West Warwick RI 02893. Precharge equal to static supply pressure ST-5 and above. Each tank shall be AMTROL Therm-X-Trol Model No.

Hydronic Expansion Tank Sizing. This was at one time an old gravity system and was changed when the boiler was changed about 8 years ago. Select 40 50 60 80 120 Gallons.

10 - 20000 Min Operating Temp F Max Operating Temp F Antifreeze Glycol Concentration Min Operating Pressure. Domestic Hot Water Volume. Amtrol Products are made in the USA at our ISO registered facilities by American workers dedicated to producing the highest quality expansion tanks in the world.

Accurate Critical Sizing Is A Must When selecting and sizing hydro. Amtrol SELECTION TOOLS. ST-1 for Tankless and Point-Of-Use POU Heaters up to 2 gallons.

150 psi T. THERMAL EXPANSION TANK SIZING. ASME Water Heater On Expanded Water enters the ASME Therm-X-Trol ASME Therm-X-Trol Backflow Preventer Expanded Water 1400 Division Road West Warwick RI 02893 T.

They have about 8 loops or sections each. Finned copper baseboard convectorsunit heaters cast iron radiators or cast iron heating baseboards and the heat output of the heating boiler in 1000s of BTUs Hour or Output BTUh. Sizing the ExTROL Diaphragm-Type Hydro-Pneumatic Tank For pressurization and expansion control of low temperature water systems Accurate Critical Sizing A Must When selecting and sizing hydro-pneumatic tanks for maintaining pressurization and expansion control in engineered.

Pipes in the basement. WELL TANK SIZING. Features For use with anti-freeze fire protection.

Amtrol invented the thermal expansion tank to control pressure build-up in closed potable hot water systems. 40F incoming water temperature. This is recommended for pumps 34 hp or larger.

To use these boiler expansion tank sizing charts you need to know just the type of heating system radiation used. Hydronic Expansion Tank Sizing. Thermal Expansion Tank Sizing.

Select 40 60 80. 4 inches thick 28 inches high and about 30 inches wide. 5 - 200 Max Operating Pressure.

The tank selection is based on approximately two minutes running time. Fire-X-Trol can be used with water glycerin and propylene glycol systems. The complete handbook covers the application of hydro-pneumatics in heating plumbing cooling water supply and commercial water heating systems.

FILL-TROL Combination Packages Model. This expansion tank design guide takes you step by step through the design process of sizing and selecting an expansion tank for a chilled water system. This prevents the water heater safety relief valve from opening saving energy and expansion tanks are all made in the USA in our ISO 90012015 certified facilities.

POTABLE WATER EXPANSION TANKS American Sizing Chart For Commercial Water Heaters Water Heater Capacity in Gallons Water Temperature 30 40 50 66 82 100 120 140 AET-2 AET-2 AET-5 AET-5 AET-5 AET-10 AET-10 150 AET-2 AET-2 AET-5 AET-5 AET-5 AET-10 AET-10 160 AET-5 AET-5 AET-5 AET-5 AET-5 AET-10 AET-10 170 AET-5 AET-5 AET-10 AET-10. There are 6 loops going to 6 apartments Building size is approximately 5800 Sq Ft. Replacing an old Weil-McLain with a Burnham Series 2 299k BTU input.

To use either sizing chart on page 4 for selection 109 FILL-TROL is equivalent to 15 EXTROL 110 FILL-TROL is equivalent to 30 EXTROL 111 FILL-TROL is equivalent to 60 EXTROL and 112 FILL-TROL is equivalent to 90 EXTROL. The tank selection is based on approximately one minute running time. Select 120 140 160 F.

I have an old two story house with 10 cast Iron radiators. ESP II - Effective Sizing Protection II. Water Heater Expansion Tanks Featuring Antimicrobial Protection ST-1 for Tankless B A.

Expansion tank Invented the refrigerant gas cylinder Entered the commercial products business Invented the top coil indirect Hot Water Maker Invented the thermal expansion tank hee tankk 1954 1967 1975 1986 1991 Invented the pre-pressurized well tank Built current Rhode Island manufacturing facility Invented the indirect-red Hot Water Maker Opened the Amtrol. Amtrol Products are made in the USA at our ISO registered facilities by American workers dedicated to producing the highest quality expansion tanks in the world. ESP I - Effective Sizing Protection I.

Expansion Tanks Made in the USA InSight. An Amtrol Fill-Trol expansion tank that incorporates a. Therm-X-Trol Quick Sizing Charts Sizing based on.

Our sizing tools help you select the right product for your application. This data has been excerpted from AMTROLs Engineering Handbook - Chapter Two Section B Hydro-pneumatics in Hot Water Heating Systems. 2 How It Works.

GPM OPERATING PRESSURE 3050. It starts with background on the chilled water system then solves for the total chilled water volume within the system based on the piping and equipment and uses the total volume pipe expansion coefficient. Fire-X-Trol expansion tanks prevent damage to fire protection systems by accommodating the expanded volume of system fluids that result from temperature changes.

There are 2 inch 1-12 and inch galv. This is recommended for pumps up to 34 hp. Amtrol expansion tank size.

The sizing charts below and select a Therm-X-Trol. WELL TANK SIZING. Pump Discharge Rate Approx.

This keeps the system pressure below the pressure limitations of the system components. Thermal Expansion Tank Sizing. 2 The EXTROL System.